Gas boiler power consumption and UPS sizing

Real boiler consumption from datasheets, and battery sizing for a 4–24 hour UPS.

Quick answer

A boiler draws 60–150 W. Running a 100 W boiler for 8 hours needs ≈ 1.13 kWh: a 12 V LiFePO₄ battery of ≈ 89 Ah or AGM of ≈ 170 Ah.

Prefilled for a 100 W boiler, 8 hours, 12.8 V LiFePO₄. For AGM set usable share to 50% and voltage to 12 V.

W

Average power used by your devices, not the maximum rating of your inverter.

h
V

Use the nominal voltage on your battery label. LiFePO₄ batteries commonly use 12.8 / 25.6 / 51.2 V.

Losses & available energy
%

90% is a starting assumption. Efficiency depends on the inverter and its load.

%

The fraction of nominal energy you plan to use. Allow for starting charge, reserve and battery limits.

W

Separate inverter losses. If already included in your efficiency figure, leave this at 0 W.

Estimated result

Required nominal capacity

—kWh

Average power use
—
Battery power draw
—

An estimate for your inputs. Actual performance depends on temperature, battery condition and changing loads.

Capacity alone does not establish compatibility. Check battery voltage, battery and BMS current limits, startup loads and inverter specifications.

How much electricity a gas boiler uses

Gas heats the water; electricity runs the controls, the fan (on room-sealed boilers) and the pump. Consumption is small, but without it the boiler stops.

Indicative values from wall-hung boiler datasheets. Check your own model’s manual.
ComponentTypical
Electronics & fan30–100 W
Circulation pump25–90 W
Total while running60–150 W, some models up to ≈ 200 W
Standby≈ 5 W

For example, the De Dietrich Evodens datasheet lists 84–92 W of auxiliary power plus 40–43 W for the pump, and 5 W at zero load.

What battery a boiler UPS needs

Capacity (Ah) = (load ÷ efficiency + idle) × hours ÷ (usable share × voltage)
100 W boiler, 85% UPS efficiency, 10 W self-consumption. Lead-acid batteries shouldn’t be discharged below 50%.
Backup timeLiFePO₄ 12.8 V (90%)AGM / gel 12 V (50%)
4 h44 Ah85 Ah
8 h89 Ah170 Ah
12 h133 Ah255 Ah
24 h266 Ah511 Ah

Boilers cycle, so real backup time is usually longer than the table. Treat it as a conservative cold-night estimate.

How to choose a boiler UPS

  • Pure sine wave only. The pump and control board don’t tolerate modified sine output.
  • UPS rating 2–3× the boiler’s consumption, to cover the pump’s start-up current.
  • Charging current. Cheap units charge at 1–2 A, so a 100 Ah battery won’t refill between outages. Look for 10 A or more.
  • 12 V or 24 V battery bank. For 24 V, two batteries go in series and the Ah in the table can be halved.
  • An alternative is a power station with a UPS function (e.g. BLUETTI AC180): pricier, but no separate battery or installation.

Estimates only; actual runtime is not guaranteed. Always check your equipment specs and the manufacturer’s instructions.

Frequently asked questions

Can I use a power station instead of a UPS?

Yes, if it outputs a pure sine wave; stations with a UPS function also switch over automatically. See the BLUETTI AC180 page for a worked example.

Why does the boiler shut down or show an error on a UPS?

Most common causes: modified sine output, a phase-sensitive boiler, or missing earth. Check the UPS type and contact the boiler’s service engineer.

LiFePO₄ or AGM for a boiler?

LiFePO₄ costs more up front but gives almost twice the usable energy per Ah and lasts thousands of cycles. AGM is cheaper but wears out quickly with daily outages.