Step 1. Work out your average load
List what must keep running during an outage and add up the average power. For a fridge use daily kWh ÷ 24, not the compressor rating.
- Router and ONT: 10–15 W
- LED bulbs: 5–10 W each
- Phone charging: ≈ 10 W on average
- Fridge: 20–50 W on average
- Laptop: 30–65 W
- Gas boiler: 60–150 W
Step 2. Pick capacity for your outage length
| Load set | 4 h | 8 h | 12 h |
|---|---|---|---|
| Basics: router, lights, phones (≈ 40 W) | 0.3 kWh | 0.6 kWh | 0.8 kWh |
| Comfort: + fridge, laptop (≈ 120 W) | 0.7 kWh | 1.4 kWh | 2.1 kWh |
| With a gas boiler (≈ 220 W) | 1.2 kWh | 2.4 kWh | 3.7 kWh |
| Station class | Good for | Examples |
|---|---|---|
| up to 0.5 kWh | Router and phones for 4–8 h | small 256–512 Wh stations |
| 0.7–1.2 kWh | Comfort for 4–6 h or basics for a day | RIVER 2 Pro, DELTA 2, AC180 |
| 2 kWh and up | Comfort overnight, boiler for 8+ h | DELTA 2 + Extra Battery and larger stations |
Step 3. Check the output power
Inverter output must exceed everything switched on at once, including start-up surges. 800 W is enough for an apartment without a kettle or microwave; boiling a kettle needs 1,800–2,400 W.
What else matters
- Charging speed. With rolling outages the power may be back for only 2–4 hours: stations charging at 1,000–1,400 W refill in an hour or so.
- LiFePO₄ chemistry: thousands of cycles and safer than standard lithium-ion.
- UPS/EPS mode: the station stays plugged in and switches over by itself.
- Expandable capacity with an extra battery, in case outages get longer.
Estimates only; actual runtime is not guaranteed. Always check your equipment specs and the manufacturer’s instructions.