Start with total load in watts and required backup time. Amp-hours alone are not enough: battery voltage determines stored energy too.
Worked example
Example: a 200 W load for 5 hours needs 1 kWh of AC energy. With 90% inverter efficiency and 80% usable depth of discharge, nominal capacity is 1 ÷ (0.9 × 0.8) ≈ 1.39 kWh. At 12 V this is about 116 Ah.
What affects the result
Check BMS current limits, surge loads, battery chemistry, cabling, fuses and charger compatibility. High-current installation should be designed by a qualified professional.
Frequently asked questions
Are 100 Ah at 12 V and 24 V the same?
No. 12 V × 100 Ah ≈ 1.2 kWh; 24 V × 100 Ah ≈ 2.4 kWh before losses.
Estimates are not a guarantee of actual runtime. Always check equipment specifications.